DSE 4520



DSE 4520

Auto Mains Failure (AMF) CONTROLLER

»  Alternator frequency & CAN speed sensing in one variant
»  Largest back-lit icon display in its class
»  Heated display option
»  Real time clock provides accurate event logging
»  Extremely efficient power save mode
»  Engine pre-heat
»  Engine run-time scheduler
»  Engine idle control for starting & stopping
»  Start on low battery voltage
»  3 phase generator sensing
»  3 phase mains (utility) sensing (DSE4520 MKII only)
»  Compatible with 600 V ph to ph nominal systems
»  Generator/load power monitoring (kW, kV A, kV Ar, pf)
»  Accumulated power monitoring (kWh, kVA h, kVAr h)
»  Generator overload protection (kW)
»  Generator/load current monitoring and
protection
»  Engine hours counter
»  Battery voltage monitoring
»  Comprehensive warning, electrical trip or shutdown protection upon fault condition
»  Under / Over Speed (with CAN only)
»  Low Oil Pressure
»  High Coolant (Water) Temperature
»  Low Fuel Level
» Emergency Stop
»  Charger Alternator Fail
»  Low / High Battery Voltage
»  Mains Under / Over Voltage Protection (27/59)
»  Mains Under / Over Frequency Protection (81U/O)
»  Generator Under / Over Voltage Protection (27/59)
»  Generator Under / Over Frequency Protection (81U/O)
»  Generator Over Current Protection (50+51)
»  Generator Over Load Protection (KW)
»  1 alternative configuration
»  Configurable remote start input
»  3 engine maintenance alarms
»  Event log (50)
»  Fully configurable via the fascia or PC using USB communication


  Dimension Details:
  • Over All Dimension - 140 mm x 113 mm x 43 mm
  • Panel Cut Out Dimension - 118 mm x 92 mm

Hardware


  Frequency Range – 3.5 to 75Hz

  DC Supply (Continuous Voltage Rating) – 8V to 35V

  Mains Utility DSE 4520 MK-II Only (Voltage Range)
  • 15 V to 415 V AC (Ph to N)
  • 26 V to 719 V AC (Ph to Ph)


  Fuel and start outputs (configurable when using CAN)



  4 configurable DC outputs

  3 configurable analogue/digital inputs

  4 configurable digital inputs

  Configurable staged loading outputs

  LCD alarm indication

Standards


Test

Reference Standards

ELECTRO-MAGNETIC COMPATIBILITY

  • EMC Generic Immunity Standard for the Industrial Environment
  • EMC Generic Emission Standard for the Industrial Environment

 

  • BS EN 61000-6-2
  • BS EN 61000-6-4

ELECTRICAL SAFETY

  • Safety of Information Technology Equipment, including Electrical Business Equipment

 

  • BS EN 60950

TEMPERATURE

  • Ab/Ae Cold Test -30 oC
  • Bb/Be Dry Heat +70 Oc

 

  • BS EN 60068-2-1
  • BS EN 60068-2-2

VIBRATION

  • Ten sweeps in each of three major axes

 

  • BS EN 60068-2-6

HUMIDITY

  • Db Damp Heat Cyclic 20/55 Oc at 95% RH 48 Hours
  • Cab Damp Heat Static 40 oC at 93% RH 48 Hours

 

  • BS EN 60068-2-30
  • BS EN 60068-2-78

SHOCK

  • Three shocks in each of three major axes 15 gn in 11 Ms

 

  • BS EN 60068-2-27

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES

  • IP65 - Front of module when installed into the control panel with the optional sealing gasket.

 

  • BS EN 60529