DSE 3110


DSE 3110

Engine Control Unit / Auto Start Controller

»  CAN and Magnetic Pick-up/Alt. versions available (specify on ordering)
»  Power Save mode
»  Back-lit icon LCD display
»  Remote Start input
»  Engine pre-heat
»  Generator voltage display
»  Generator frequency display
»  Battery voltage display
»  Engine speed display
»  Hours counter
»  Under / Over Speed (with MPU only)
»  Low Oil Pressure (Switch input)
»  Low Fuel Level (Switch input)
»  Emergency Stop
»  Charger Alternator Fail
»  Low / High Battery Voltage
»  Front panel editing
»  LED and LCD alarm indication
»  6 Configurable Digital inputs
»  4 Configurable Outputs (2 configurable on Magnetic Pick up/Alt., 4 configurable on CAN version)
»  Configurable timers and alarms
»  Alternative configuration
»  Comprehensive shutdown or warning on fault condition
»  DSE Configuration Software Suite through Back USB Port


  Dimension Details:
  • Over All Dimension - 98 mm x 79 mm x 40 mm
  • Panel Cut Out Dimension - 80 mm x 68 mm

DSE 3110


CAN : For use with electronic engines only.

MPU : For use with non-electronic engines only (magnetic pick-up/alternator sensing).

Hardware


  Frequency Range – 10000Hz (max)

  Generator Voltage Range – 15V – 333V AC (L-N)

  Pulse Pickup Voltage Range - ±3.5V to 75V



  DC Supply (Continuous Voltage Rating) – 8V to 35V

  LCD alarm indication

Standards


Test

Reference Standards

ELECTRO-MAGNETIC COMPATIBILITY

  • EMC Generic Immunity Standard for the Industrial Environment
  • EMC Generic Emission Standard for the Industrial Environment

 

  • BS EN 61000-6-2
  • BS EN 61000-6-4

ELECTRICAL SAFETY

  • Safety of Information Technology Equipment, including Electrical Business Equipment

 

  • BS EN 60950

Temperature

  • Ab/Ae Cold Test -30 oC
  • Bb/Be Dry Heat +70 Oc

 

  • BS EN 60068-2-1
  • BS EN 60068-2-2

VIBRATION

  • Ten sweeps in each of three major axes

 

  • BS EN 60068-2-6

HUMIDITY

  • Db Damp Heat Cyclic 20/55 Oc at 95% RH 48 Hours
  • Cab Damp Heat Static 40 oC at 93% RH 48 Hours

 

  • BS EN 60068-2-30
  • BS EN 60068-2-78

SHOCK

  • Three shocks in each of three major axes 15 gn in 11 Ms

 

  • BS EN 60068-2-27

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES

  • IP65 - Front of module when installed into the control panel with the optional sealing gasket

 

  • BS EN 60529