CSE PRO F-300



CSE PRO F 300

CSE PRO family of protective relays are advance numerical relays that provide multi protection and monitoring with reliable and fast protection solutions in a single unit.

In this family of CSEPRO series, the CSEPROF is an advanced feeder protection solution which has fast, sensitive and secure protection for feeder faults.

CSEPROF also provides an automation solution of power control. It complies with IEC 60870-5-103, IEC 61850, Modbus protocol for high integration of protection & control.

Key Features

»  Digital Signal Processor based numeric design
»  Measures true RMS with DFT filter
»  1A & 5A Rated CT Input( Site Selectable)
»  PT Configuration (Star & Delta & 63.5/110V)
»  Draw out enclosure with CT shorting Link
»  Measurement, Protection & Metering.
»  SCADA Communication (USB & RS 485 / Rs 485)
»  Mulit Protocol Communication: (Modbus / Ethernet / IEC 60870-5 -103 / IEC 61850)
»  Disturbance Record.
»  DI/DO Programmable Matrix.
»  Intelligent key for DI status & DO status, details of fault pickup & status of last fault occurred.
»  Last 10 fault record (non-volatile memory) with time stamp.
»  Last 100 event record (non-volatile memory) with time stamp.
»  Self supervision function


  3 phase time Over Current protection (50/51)

  Instantaneous Over Current High Set (50)

  IMDT / DEFT Earth Fault protection (51N)

  Instantaneous Over Current High Set (50N)

  Breaker Failure Protection (50BF)

  Current Unbalance (46)

  Broken Conductor Detection (46BC)

  Auto Recloser (79)

  Cold Load Pickup (62CLD)

  Under/ Over Voltage (27/59)

  Residual Voltage / Voltage Unbalance (59N/47)

  Trip Circuit Supervision (74TC).

  Voltage Controlled Over Current (51V)

  Under Current (37P)

  Restricted Earth Fault (87G)

  Reverse Power (32R)

CSEPROF-300-1-M-L-Z


CSEPROF-300-1-M-L-Z


Hardware


  1A & 5A common current terminal & programmable.

  4 Current Analog Input

  3 Voltage Analog Input.

  Max. 6 Digital Inputs.

  Max. 6 Digital Outputs.

  Aux Supply:

    » H Model – 85V-280V AC / 110V-300V DC
    » L Model – 18V-60V DC



  8 LED’s at Pkup & Trip on fault + 3 LED’s with special function of 3 control keys.

  LAN-RJ45/RS-485/USB ports for Communication.

  16x4 Alpha numeric LCD.

  8 Push button on the front for MMI.

  Dimension Details:

    » Cut Out Dimension: 145 (H) x 112 (W)
    » All over Dimension: 156 (H) x 125 (W) x 249 (D)

Standards


Test

Reference Standards

Design Standards

IEC 60255-22-(1-6) & 5

High Voltage Test

  • High Frequency Interferences Test
  • Dielectric Voltage Test 
  • Impluse Voltage Test

EMC Immunity Test

  • Fast Transient Disturbance Immunity Test
  • Surge Immunity Test
  • Electrical Discharge Immunity Test
  • Radiated Immunity Test
  • Conducted immunity Test
  • Power Frequency Magnetic Field immunity Test
  • EMC Emission Tests(Radio Interference Suppression Test
  • Radio Interference Radiation Test

Environmental Tests

  • Temperature
  • Test Bd: Dry Heat
  • Test Db: Damp Heat(Cyclic)

Mechanical Tests

  • Vibration Response Test
  • Vibration Endurance Test
  • Shock Tests
  • Shock Endurance Test

 

IEC 60255-22-1 Class 3
IEC 60255-5 / EN 50178
IEC 60255-5

IEC60255-22-4/61000-4-4 Class 4
IEC 61000-4-5 Class 4
IEC 60255-22-2 / IEC 61000-4-2
EN 61000-4-3 / IEC 60255-22-3
EN 61000-4-6 / IEC 60255-22-6
IEC 61000-4-8
IEC 60255-25/EN55011/CISPR11
IEC 60255-25/EN55011/CISPR11

IEC 60068-2-1/2
IEC 60068-2-2
IEC 60068-2-30

 

IEC 60068-2-6/IEC 60255-21-1 Cl 1
IEC 60068-2-6/IEC 60255-21-1 Cl 1
60068-2-27/ 60255-21-2 Class 1
60068-2-29/ 60255-21-2 Class 1